Voltage Protection Relay Instruction Manual

Short Description:

Voltage Protection Relay Instruction Manual•GeneralMicroprocessor controlled. Three or single phase relay is used in systems exposed to over or under voltage, such as command, control or compensation systems and protects devices such as condensers, motors, air conditioners and compressors. It is di


Product Detail

Voltage Protection Relay Instruction Manual

•General

Microprocessor controlled. Three or single phase relay is used in systems exposed to over or under voltage, such as command, control or compensation systems and protects devices such as condensers, motors, air conditioners and compressors. It is divided into sub-categories depending on the voltage adjustment range, on or off start modes.


image.png


MeasurementandSupplyCircuit

Supply Voltage (Un)


:220,230V AC

:400V AC

Supply Frequency

:50 Hz.

Power Consumption (max.)

:30VA/2W(50 Hz).

Measurement Method

:True RMS

Settings


Over Voltage Setup (Umax.)

1,05...1,30xUn (% Scale)

231 ...286 VAC

420 ...520 VAC


Under Voltage Setup (Umin.)


0,7...0,95xUn (% Scale)

154...209 VAC

.380VAC 

Hysteresis (for Umax and Umin)

1%x Un
Delay-Off(Delay) Toff

0.1... 20 sec.(>1.3*Un or0.7*Un,0.1Sec)

Delay-On (Reset Delay) Ton

0.1... 20 sec.

Voltage Adjustment Accuracy

± 3%

Repetition Accuracy(Voltage)

± 0.5%

Accuracy of the Set Times Repetition Accuracy (Time)

± 5% + 100 msec. ±3%

Output
Output Type

:1 inverter, 8A, 250V, 2000VA (Cos =1)

Electrical Life

105

Mechanical Life

107

Ambiant Conditions

Operating Temperature

:-5°C... +55°C

Relative Humidity

:<%90 (without condensation)

Connection


Cable Cross-sections for Terminals

4mm2 (12AWG) stranded rigid cable 6mm2 (10AWG) solid conductor cable 2x2.5mmz (14AWG) solid conductor cable

Screw-On Force

0.5 Nm (4.5in.lbs)

Body

Installation

:Inside the panel vertically or on to the rail

Material Type

:Plastic Consistent with UL 94 VO

Protection Class

:IP 20 (Terminals), IP40 (Front Panel)

Dimensions

:Type PK 28

Weight

:100gr.

Isolation

Isolation Voltage (EN 60255-5)

:400V

Isolation Coordination (EN 60255-5)

:Exceeding Voltage Category III, Pollution Degree 3

Instant Burst Voltage (EN 60255-5)

:4 kV 1.2/50 uS

Dielectric Resistance (EN 60255-5)

:2kVAC50 Hz. 1 minute.

Isolation Resistance (EN 60255-5)

: >500 MOHM/500VDC

Followed Standards

EN-60255-6

Product Standard

EN-61000-6-2

Immunity

EN-61000-6-3, EN-61000-64

Emission

Di recti ves/Regulations To Be Followed

73/23/EEC

LVD

89/336/EEC

EMC








image.png

• Function description:

Voltage normal:

When three-phase voltage is normal, the "OUT"LED flash seconds. After the fault recovery time , setting by potentiometer "Ton", “OUT"LED turns on, and relay is closed.

Overvoltage:

When any line voltage is overvoltage, overvoltage fault indicator ">Un”LED flash seconds.Reaching the fault delay time which setting by "Toff”, relay disconnect, "OUT”LED turn off and Overvoltage failure indicator "〉Un”LED is turn on.If power recover to normal before the fault delay time ,then relay and "OUTLED are not act, still closed; When the overvoltage value is 1.3 times higher, without delay, relay immediately disconnect, Overvoltage failure "〉Un”LED turns on.

Undervoltage:

When any line voltage is undervoltage, undervoltage fault in dicator "vUn''LED flash seconds. Reaching the fault delay time which setting by "Toff, relay disconnect, “OUT'LED turn off,Undervoltage indicator "vUif'LED is turn on.If power recover to normal before the fault delay time ,then relay and "OUT”LED are not act, still closed; When the undervoltage value is 0.7 times lower, without delay, relay immediately disconnect, Undervoltage indicator "<Un”LED turns on

Recover to normal:

When the voltage recover from the fault status to normal, the "OUT"LED flash seconds.fault recover time which is setting by "Ton” has reached,then relay close and output, "OUT'LED turn on; If overvoltage or undervoltage happen before the reaching of fault recovery time ,then relay and "OUT'LED are not act, still disconnected; Over voltage or under voltage indicator light on.

Phase Sequence:

When Phase sequence errors, the OUT light is off, the relay de-energizes its contact.